surge protection, lightning protection, hescorls.com
   
 

Our Products > Traffic Control > HE30

 
 
HE30
 
 >> print ready pdf
 
Description

The HE30 Series is a two-stage, hybrid surge suppressor designed for use on data or communication circuits where surges of 10KA (8 x 20uS) or less are anticipated. This device will provide continuous and reliable protection for all of your sensitive electronics.

The #10 stud is used for mounting HE30 and serves as the grounding mechanism to ensure proper grounding of the internal protection scheme. Care should be taken to provide a clean, conductive surface that is bonded to earth ground and mounted as close as possible to the lines to be protected.

The HE30A is a polarized unit designed to be used on low voltage DC signal lines. This unit has a black and yellow color-coded input pair, with a red and green output pair.

The HE30C is a non-polarized unit designed for use on low voltage DC signal lines. This unit has a black and yellow color-coded input pair, with a red and green output pair.

The standard HE30 second stage clamp is from each line to ground (A) except in cases where the ground potential may vary. In this case, a line-to-line second stage clamp would be preferred.

 

Specifications 

Peak Surge Current 8 x 20us........................................10KA
Occurrences............................................100 typical @ 2KA
Response Time..............................................................<1nS
Voltage Clamp....................................8 ,12, 20, 30 or special
Series Impedance..........................................................none
Energy..................................................................250 Joules
Continuous Current............................................100mA max.
Operating Temperature.................................-40°C to +85°C
Weight.........................................................................1.7 Oz.
Dimensions (In.).................................................1” x 1” x.75”
Mounting................................................Stud #10-32 x ½ In.

 
 
Features 

  • Lightning Protection for Balanced Low Voltage Signal Lines
  • Common and Differential Mode
  • Two-Stage Protection
  • Installs Easily
  • Self Restores
  • Fast Response Time
  • Flame Retardant Epoxy Encapsulated
  • Selectable Clamp Voltages
  • Compact in Size

 
Installation


 
Ordering Information

The HE30 Series suppressor part numbers consist of four major parts. These are the model, polarity, voltage and second stage clamp configuration. Be sure to specify all four requirements when placing orders